1. The drawing of terminal block wiring diagrams and phase connection tables shall comply with the provisions of GB6988.6-1993 "Drawing of Functional Tables for Control Systems";
2. All terminals and their leads shall be labeled with text symbols and wiring numbers consistent with those in the electrical schematic diagram. The compilation of item codes, terminal numbers, and wire numbers in the schematic diagram shall comply with the provisions of GB5094-1985 "Item Codes in Electrical Technology", GB4026-1992 "General Rules for Identification and Application of Alphanumeric Systems for Terminal Blocks and Specific Wire Ends of Electrical Equipment", and GB4884-1985 "Marking of Insulated Wires", etc.;
3. Unlike electrical schematic diagrams, in terminal block wiring diagrams, all parts (contacts, coils, etc.) of the same terminal block must be drawn together;
4. Terminal block wiring diagrams shall be drawn using fine lines. Wiring methods are divided into front-panel wiring and rear-panel wiring. Front-panel wiring is generally used. For simple electrical control components with a small number of terminals and uncomplicated wiring relationships, the connections between components can be drawn directly. For complex components with a large number of terminals and complex wiring, wiring ducts are generally used. Only the terminal numbers need to be marked; it is not necessary to draw the connections between components.
5. The wiring diagram should indicate the type, specifications, cross-sectional area, and color requirements of all wires used for wiring.
6. When connecting components to external circuits, large-section wires should preferably be connected using connectors; other wires should be connected via terminal blocks.